Table 192: CONTROL output signals
Name Type Description
OFF BOOLEAN Control output OFF
LOCAL BOOLEAN Control output Local
STATION BOOLEAN Control output Station
REMOTE BOOLEAN Control output Remote
ALL BOOLEAN Control output All
BEH_BLK BOOLEAN Logical device CTRL block
status
BEH_TST BOOLEAN Logical device CTRL test sta-
tus
3.17.11.9 Settings
Table 193: Non group settings
Parameter Values (Range) Unit Step Default Description
LR control
1=LR key
2=Binary input
1=LR key LR control through LR key or binary
input
Station authority
1=L,R
2=L,S,R
3=L,R,L+R
4=L,S,S+R,L+S,L
+S+R
1=L,R Control command originator cate-
gory usage
Control mode
1=On
2=Blocked
5=Off
1=On Enabling and disabling control
3.17.11.10 Monitored data
Table 194: Monitored data
Name Type Values (Range) Unit Description
Command
response
Enum
0=No commands
1=Select open
2=Select close
3=Operate open
4=Operate close
5=Direct open
6=Direct close
7=Cancel
8=Position reached
9=Position timeout
Latest command re-
sponse
Table continues on the next page
1MRS758755 C Basic functions
REC615 & RER615
Technical Manual
171