Loading...
Table 221: Port mode settings
Parameter Values (Range) Unit Step Default Description
Port 1 Mode
Off
On
On
Mode selection for rear port(s). If port is not used,
it can be set to “Off”.
Port 2 Mode
Off
On
On Mode selection for rear port(s). If port is not used,
it can be set to “Off”. Port cannot be set to “Off
when
Redundant mode
is “HSR” or “PRP” and port
is one of the redundant ports (LAN A or LAN B).
Port 3 Mode
Off
On
On Mode selection for rear port(s). If port is not used,
it can be set to “Off”. Port cannot be set to “Off
when
Redundant mode
is “HSR” or “PRP” and port
is one of the redundant ports (LAN A or LAN B).
3.20.2.5 Monitored data
Monitored data is available in six locations.
Monitoring> Communication> Ethernet> Activity> CH1LIV
Monitoring> Communication> Ethernet> Activity> CH2LIV
Monitoring/> Communication> Ethernet> Activity> CH3LIV
Monitoring/> Communication> Ethernet> Link statuses> LNK1LIV
Monitoring> Communication> Ethernet> Link statuses> LNK2LIV
Monitoring> Communication> Ethernet> Link statuses> LNK3LIV
1MRS758755 C Basic functions
REC615 & RER615
Technical Manual
213