Parameter Values (Range) Unit Step Default Description
Amplitude Corr A 0.9000...1.1000 0.0001 1.0000 Phase A Voltage phasor magnitude
correction of an external voltage
transformer
Amplitude Corr B 0.9000...1.1000 0.0001 1.0000 Phase B Voltage phasor magnitude
correction of an external voltage
transformer
Amplitude Corr C 0.9000...1.1000 0.0001 1.0000 Phase C Voltage phasor magnitude
correction of an external voltage
transformer
Division ratio 1000...20000 1 10000 Voltage sensor division ratio
Voltage input type 1=Voltage trafo
3=CVD sensor
1=Voltage trafo Type of the voltage input
Angle Corr A -20.0000...20.0000 deg 0.0001 0.0000 Phase A Voltage phasor angle cor-
rection of an external voltage trans-
former
Angle Corr B -20.0000...20.0000 deg 0.0001 0.0000 Phase B Voltage phasor angle cor-
rection of an external voltage trans-
former
Angle Corr C -20.0000...20.0000 deg 0.0001 0.0000 Phase C Voltage phasor angle cor-
rection of an external voltage trans-
former
Basic functions 1MRS758755 C
44 REC615 & RER615
Technical Manual