4.4.5.7 Settings
PSPTUV Group settings
Table 469: PSPTUV Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.010...1.200 xUn 0.001 0.500 Start value
Operate delay time 40...120000 ms 10 40 Operate delay time
Table 470: PSPTUV Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Voltage block value 0.01...1.00 xUn 0.01 0.20 Internal blocking
level
Enable block value
0=False
1=True
1=True Enable Internal
Blocking
Table 471: PSPTUV Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 472: PSPTUV Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Relative hysteresis 1.0...5.0 % 0.1 4.0 Relative hysteresis
for operation
4.4.5.8 Monitored data
PSPTUV Monitored data
Table 473: PSPTUV Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
PSPTUV Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS758755 C Protection functions
REC615 & RER615
Technical Manual
447