EasyManua.ls Logo

ABB Relion RER615 - Page 514

ABB Relion RER615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 259: The behavior of fault distance estimate in time
5.4.4.4 Alarm indication
SCEFRFLO contains an alarm output for the calculated fault distance. If the
calculated fault distance FLT_DISTANCE is between the settings
Low alarm Dis limit
and
High alarm Dis limit
, the ALARM output is activated.
The ALARM output can be utilized, for example, in regions with waterways or other
places where knowledge of certain fault locations is of high importance.
Figure 260: An example of the ALARM output use
Protection related functions
1MRS758755 C
514 REC615 & RER615
Technical Manual

Table of Contents

Other manuals for ABB Relion RER615

Related product manuals