Table 652: CBXCBR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation mode
on/off
Select timeout 10000...300000 ms 10000 30000 Select timeout in
ms
Pulse length 10...60000 ms 1 200 Open and close
pulse length
Control model
0=status-only
1=direct-with-nor-
mal-security
4=sbo-with-en-
hanced-security
4=sbo-with-en-
hanced-security
Select control mod-
el
Operation timeout 10...60000 ms 1 500 Timeout for nega-
tive termination
Identification CBXCBR1 switch
position
Control Object
identification
Table 653: CBXCBR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Operation counter 0...10000 1 0 Breaker operation
cycles
Adaptive pulse
0=False
1=True
1=True Stop in right posi-
tion
Event delay 0...10000 ms 1 200 Event delay of the
intermediate posi-
tion
Vendor 0 External equipment
vendor
Serial number 0 External equipment
serial number
Model 0 External equipment
model
9.1.7.2 DCXSWI Non group settings
Table 654: DCXSWI Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation mode
on/off
Select timeout 10000...300000 ms 10000 30000 Select timeout in
ms
Pulse length 10...60000 ms 1 100 Open and close
pulse length
Control model
0=status-only
1=direct-with-nor-
mal-security
4=sbo-with-en-
hanced-security
4=sbo-with-en-
hanced-security
Select control mod-
el
Operation timeout 10...60000 ms 1 30000 Timeout for nega-
tive termination
Identification DCXSWI1 switch
position
Control Object
identification
Control functions 1MRS758755 C
636 REC615 & RER615