t s
A
I
I
E
B k
c
[ ]
=
>
+
(Equation 78)
t[s] Operate time (in seconds)
A set
Curve parameter A
B set
Curve parameter B
C set
Curve parameter C
E set
Curve parameter E
I Measured current
I> set
Start value
k set
Time multiplier
11.2.1.3 RI and RD-type inverse-time characteristics
The RI-type simulates the behavior of electromechanical relays. The RD-type is an
earth-fault specific characteristic.
The RI-type is calculated using the formula
t s
k
I
I
[ ]
. .
=
×
>
0 339 0 236
(Equation 79)
The RD-type is calculated using the formula
t s
I
k I
[ ] . .= ×
× >
5 8 1 35 In
(Equation 80)
t[s] Operate time (in seconds)
k set
Time multiplier
I Measured current
I> set
Start value
General function block features 1MRS758755 C
762 REC615 & RER615
Technical Manual