GUID-9BC3D595-CF08-42AF-B74E-0D3970A552DB V1 EN-US
Figure 33: Active setting group
2.
Select the setting group with or .
3.
Press to confirm the selection or to cancel.
4. Commit the settings.
Remember to document the changes you make.
7.3.1.2 Browsing and editing setting group values
GUID-5624E7E4-1D14-469A-BF86-8BD560B72F9D v5
1.
Select Main menu /Settings/IED Settings and press
.
Setting group 1 is the default setting group to be edited.
IEC13000054 V2 EN-US
Figure 34: Selecting a setting group for editing
2.
Press on the Setting group line in the dialog box to activate selection mode.
3.
Select the wanted setting group with
or and press .
GUID-5196A07A-9DAF-4696-8773-F52ADC155C44 V1 EN-US
Figure 35: Changing the setting group
4.
Select Yes in the dialog, and press to continue.
The current setting group is displayed on the left in the header.
5.
Select the application function category in the list with or , and press to see the
function blocks in that category.
Categories available in the list depend on the configuration configured with PCM600.
1MRK 500 131-UEN Rev. C Section 7
Operating procedures
Switchgear control unit SAM600-IO 47