Table 2: Plug-in unit and case
Main unit Slot ID Content options
Plug-in
unit
- HMI Small (4 lines, 16 characters)
X100 Auxiliary
power/BO module
48...250 V DC/100...240 V AC; or 24...60 V DC
2 normally-open PO contacts
1 change-over SO contact
1 normally-open SO contact
2 double-pole PO contacts with TCS
1 dedicated internal fault output contact
Case
X130 AI/BI module 3 phase voltage inputs (60...210 V)
1 residual voltage input (60...210 V)
1 voltage measurement input (60...210 V)
4 binary inputs
X000
Optional
communication
module
See technical manual for details about different type of
communication modules.
Rated values of the current and voltage inputs are basic setting parameters of the
protection relay. The binary input thresholds are selectable within the range 16…176
V DC by adjusting the binary input setting parameters.
See the installation manual for more information about the case and
the plug-in unit.
The connection diagrams of different hardware modules are presented in this manual.
Table 3: Number of physical connections in configuration
Conf.
Analog channels Binary channels
CT VT BI BO
A - 5 4 6
2.4 Local HMI
The LHMI is used for setting, monitoring and controlling the protection relay. The
LHMI comprises the display, buttons, LED indicators and communication port.
1MRS758335 B Section 2
REU611 overview
REU611 11
Application Manual