3.4.3.3 Functional diagrams for control
OR
X100 PO3
OSWGAPC1
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
IN_12
IN_13
IN_15
IN_14
X100 PO4
MASTER TRIP #1
MASTER TRIP #2
OR
OR
SELGAPC3
OUT_6
IN_2
SELGAPC3
OUT_5
IN_1
TRIP
CL_LKOUT
BLOCK
RST_LKOUT
TRPPTRC1
OPERATE
TRIP
CL_LKOUT
BLOCK
RST_LKOUT
TRPPTRC2
OPERATE
CBXCBR1_EXE_OP
SELGAPC1_External Trip
PHPTOV1_OPERATE
PHPTOV2_OPERATE
PHPTOV3_OPERATE
PHPTUV1_OPERATE
PHPTUV3_OPERATE
ROVPTOV1_OPERATE
ROVPTOV2_OPERATE
ROVPTOV3_OPERTAE
NSPTOV2_OPERATE
PSPTUV1_OPERATE
PSPTUV2_OPERATE
FRPFRQ1_OPERTAE
FRPFRQ2_OPERTAE
PHPTUV2_OPETATE
NSPTOV1_OPERATE
SELGAPC1_External Trip
OSWGAPC2
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
IN_12
IN_13
IN_15
IN_14
PHPTOV1_OPERATE
PHPTOV2_OPERATE
PHPTOV3_OPERATE
PHPTUV1_OPERATE
PHPTUV3_OPERATE
ROVPTOV1_OPERATE
ROVPTOV2_OPERATE
ROVPTOV3_OPERTAE
NSPTOV2_OPERATE
PSPTUV1_OPERATE
PSPTUV2_OPERATE
FRPFRQ1_OPERTAE
FRPFRQ2_OPERTAE
PHPTUV2_OPETATE
NSPTOV1_OPERATE
GUID-FBD41DB4-5D20-46F7-9D09-04318A7EE553 V2 EN
Figure 22: Master trip
The operate signals from the protections and an external trip are connected to the two
trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding
master trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit
breaker from local or remote CBXCBR1_EXE_OP is connected directly to the output
contact PO3 (X100:15-19).
1MRS758335 B Section 3
REU611 standardized configuration
REU611 41
Application Manual