EasyManua.ls Logo

ABB Relion - Page 46

ABB Relion
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Channel number Channel ID text Level trigger mode
Binary channel 13 ROVPTOV3_START 1=positive or rising
Binary channel 14 FRPFRQ1_START 1=positive or rising
Binary channel 15 FRPFRQ2_START 1=positive or rising
Binary channel 16 PHPTOV_OPERATE 1=positive or rising
Binary channel 17 PHPTUV_OPERATE 1=positive or rising
Binary channel 18 ROVPTOV_OPERATE 1=positive or rising
Binary channel 19 PSPTUV/NSPTOV_OPERATE 1=positive or rising
Binary channel 20 FRPFRQ_OPERATE 1=positive or rising
Binary channel 21 SELGAPC1_Blocking 1 1=positive or rising
Binary channel 22 SELGAPC1_CB_Closed 1=positive or rising
Binary channel 23 SELGAPC1_CB_Open 1=positive or rising
Binary channel 24 SELGAPC1_External Trip 1=positive or rising
Binary channel 25 SG_1_ACT 1=positive or rising
Binary channel 26 SG_2_ACT 1=positive or rising
Binary channel 27 SG_3_ACT 1=positive or rising
Binary channel 28 SG_4_ACT 1=positive or rising
Binary channel 29 SG_5_ACT 1=positive or rising
Binary channel 30 SG_6_ACT 1=positive or rising
Binary channel 31 BUS_VT_MCB_OPEN 1=positive or rising
X120-BI3
OR
LED 7
TRIP CIRCUIT SUPERVISION
SELGAPC1
OUT_3
IN_3
TRPPTRC1_TRIP
TRPPTRC2_TRIP
TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
SELGAPC4
OUT_7
IN_13
OSWGAPC12
OR
OUT
IN_2
IN_3
SELGAPC2
OUT_1
IN_2
OUT_2
CB Open Position
GUID-EC303A9E-DD21-4501-A0C9-82EBC49AA114 V1 EN
Figure 21: Trip circuit supervision
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by
the master trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open position.
The TCS alarm indication is connected to LED 7.
Section 3 1MRS758335 B
REU611 standardized configuration
40 REU611
Application Manual

Related product manuals