Table 12: Default connections for binary outputs
Binary input Description Connector pins
X100-PO1 Close circuit breaker X100:6-7
X100-PO2 General start indication X100:8-9
X100-SO1 Overvoltage operate indication X100:10-12
X100-SO2 Undervoltage operate indication X100:13-14
X100-PO3 Open circuit breaker/trip coil 1 X100:15-19
X100-PO4 Open trip coil 2 X100:20-24
Table 13: Default connections for LEDs
LED Description
1 Overvoltage protection operated
2 Undervoltage protection operated
3 Residual voltage protection operated
4 Sequence protection operated
5 Frequency protection operated
6 Disturbance recorder triggered
7 Trip circuit supervision alarm
8 Bus VT MCB failure
3.4.2.2 Predefined disturbance recorder connections
Table 14: Predefined analog channel setup
Channel
Description
1 Uo
2 U1
3 U2
4 U3
5 U1B
Additionally, all the digital inputs that are connected by default are also enabled with
the setting. Default triggering settings are selected depending on the connected input
signal type. Typically all protection START signals are selected to trigger the
disturbance recorded by default.
3.4.3 Functional diagrams
The functional diagrams describe the default input, output, programmable LED,
switch group and function-to-function connections. The default connections can be
viewed and changed with switch groups in PCM600, LHMI and WHMI according to
the application requirements.
1MRS758335 B Section 3
REU611 standardized configuration
REU611 33
Application Manual