GOOSERCV_BIN:0 and GOOSERCV_BIN:1. The outputs are connected to block
inputs of the protection functions.
ISWGAPC9
IN
GOOSE Blocking
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
OUT_13
OUT_14
OUT_15
PHPTOV1_BLOCK
PHPTOV2_BLOCK
PHPTOV3_BLOCK
PHPTUV1_BLOCK
PHPTUV2_BLOCK
PHPTUV3_BLOCK
ROVPTOV1_BLOCK
ROVPTOV2_BLOCK
ROVPTOV3_BLOCK
FRPFRQ1_BLOCK
FRPFRQ2_BLOCK
NSPTOV1_BLOCK
NSPTOV2_BLOCK
PSPTUV1_BLOCK
PSPTUV2_BLOCK
GUID-0FCCA7F3-9413-49E1-8DF9-A46703C2DBAF V1 EN
Figure 53: ISWGAPC9
ISWGAPC10
ISWGAPC10 is used to block the circuit breaker operation from the received GOOSE
signals. ISWGAPC10 inputs are received GOOSE signals from GOOSERCV_BIN:
4 to GOOSERCV_BIN:19. The outputs are connected to block the circuit breaker's
close and open operation.
ISWGAPC10
IN
OUT_1
OUT_2
CBXCBR1_BLK_CLOSE
CBXCBR1_BLK_OPEN
GOOSE Block CB
GUID-7DC47FBA-D2C9-4696-B947-0A2C9F67C05E V1 EN
Figure 54: ISWGAPC10