Table 5.1.15.1.-1 Event masks
Event mask Code Setting range Default setting
V155 E31...E36 0...63 1
1V155 1E1...1E14 0...16383 4180
1V156 1E15...1E26 0...4095 1365
1V157 1E27...1E38 0...4095 341
2V155 2E1...2E10 0...1023 3
2V156 2E11...2E20 0...1023 0
2V157 2E21...2E28 0...255 0
Channel 0
Events always included in the event reporting:
Table 5.1.15.1.-2 Event codes E1...E7
Channel Event Description
0 E1 IRF
0 E2 IRF disappeared
0 E3 Warning
0 E4 Warning disappeared
0 E5 Emergency start activated
0 E6 Emergency start deactivated
0 E7 The thermal level has been changed via serial communication
Table 5.1.15.1.-3 Event codes E50...E51
Channel Event Description
0 E50 Relay restart
0 E51 Event buffer overflow
Events possible to mask out:
Table 5.1.15.1.-4 Event codes E31...E36
Channel Event Description Weighting
factor
Default
value
0 E31 Disturbance recorder triggered 1 1
0 E32 Disturbance recorder memory cleared 2 0
0 E33 HMI Setting password opened 4 0
0 E34 HMI Setting password closed 8 0
0 E35 HMI Communication password opened 16 0
0 E36 HMI Communication password closed 32 0
Default value of event mask V155 1