105
Channel 1
Table 5.1.15.1.-5 Event codes E1...E14
Channel Event Description Weighting
factor
Default
value
1 E1 Motor start up begins 1 1
1 E2 Motor start up ends 2 0
1E3
a)
Pickup of element 49 activated 4 1
1E4
a)
Pickup of element 49 reset 8 0
1 E5 Alarm signal from element 49 16 1
1 E6 Alarm signal from element 49 32 0
1 E7 Trip signal from element 49 activated 64 1
1 E8 Trip signal from element 49 reset 128 0
1 E9 Restart disable signal from element 49 256 1
1 E10 Restart disable signal from element 49 512 0
1 E11 Restart disable signal from element 66 1024 1
1 E12 Restart disable signal from element 66 2048 0
1 E13
b)
Restart disable activated 4096 1
1 E1 Restart disable reset 8192 0
Default value of event mask 1V155 4180
a)
The event code is not generated during motor start up.
b)
The thermal restart disable level is exceeded, the start-up time counter is full or the external restart
disable signal is active.
Table 5.1.15.1.-6 Event codes E15...E26
Channel Event Description Weighting
factor
Default
value
1 E15
a)
Pickup signal from element (48/14 PICKUP)
2
x (48/14 TDLY) or 48/14 activated
11
1 E16
a)
Pickup signal from element (48/14 PICKUP)
2
x (48/14 TDLY) or 48/14 reset
20
1 E17 Trip signal from element (48/14 PICKUP)
2
x
(48/14 TDLY) or 48/14 activated
41
1 E18 Trip signal from element (48/14 PICKUP)
2
x
(48/14 TDLY) or 48/14 reset
80
1 E19
a)
Pickup signal from element 50P activated 16 1
1 E20
a)
Pickup signal from element 50P reset 32 0
1 E21 Trip signal from element 50P activated 64 1
1 E22 Trip signal from element 50P reset 128 0
1 E23
a)
Pickup signal from element 37 activated 256 1
1 E24
a)
Pickup signal from element 37 reset 512 0
1 E25 Trip signal from element 37 activated 1024 1
1 E26 Trip signal from element 37 reset 2048 0
Default value of event mask 1V156 1365
a)
The event code is not generated during motor start up.
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610REM 610
1MRS755537