Table 5.1.15.1.-7 Event codes E27...E38
Channel Event Description Weighting
factor
Default
value
1 E27
a)
Pickup signal from element 51N activated 1 1
1 E28
a)
Pickup signal from element 51N reset 2 0
1 E29 Trip signal from element 51N activated 4 1
1 E30 Trip signal from element 51N reset 8 0
1 E31
a)
Pickup signal from element 46 activated 16 1
1 E32
a)
Pickup signal from element 46 reset 32 0
1 E33 Trip signal from element 46 activated 64 1
1 E34 Trip signal from element 46 reset 128 0
1 E35 Trip signal from element 46R activated 256 1
1 E36 Trip signal from element 46R reset 512 0
1 E37 CBFAIL activated 1024 0
1 E38 CBFAIL reset 2048 0
Default value of event mask 1V157 341
a)
The event code is not generated during motor start up.
Channel 2
Table 5.1.15.1.-8 Event codes E1...E10
Channel Event Description Weighting
factor
Default
value
2 E1 PO1 activated 1 1
2 E2 PO1 reset 2 1
2 E3 PO2 activated 4 0
2 E4 PO2 reset 8 0
2 E5 PO3 activated 16 0
2 E6 PO3 reset 32 0
2 E7 SO1 activated 64 0
2 E8 SO1 reset 128 0
2 E9 SO2 activated 256 0
2 E10 SO2 reset 512 0
Default value of event mask 2V155 3
Table 5.1.15.1.-9 Event codes E11...E20
Channel Event Description Weighting
factor
Default
value
2 E11 DI1 activated 1 0
2 E12 DI1 deactivated 2 0
2 E13 DI2 activated 4 0
2 E14 DI2 deactivated 8 0
2 E15 DI3 activated 16 0
2 E16 DI3 deactivated 32 0
2 E17 DI4 activated 64 0
2 E18 DI4 deactivated 128 0