Table 5.2.3.-4 Measuring range
Measured currents on phases I
a
,I
b
and I
c
as
multiples of the rated currents of the energizing
inputs
0...50 × I
n
(CT)
Ground-fault current as a multiple of the rated
current of the energizing input
0...8 × I
n
(CT)
Table 5.2.3.-5 Digital inputs
Rated voltage: DI1...DI2 DI3...DI5 (optional)
REM610CxxHxxx 110/125/220/250 V DC
Activating threshold Max. 88 V DC (110 V DC -
20%)
REM610CxxLxxx 24/48/60/110/125/
220/250 V DC
Activating threshold Max. 19,2 V DC (24 V DC -
20%)
REM610CxxxxMx 24/48/60/110/125/
220/250 V DC
Activating threshold Max. 19,2 V DC (24 V DC -20%)
Operating range ±20% of the rated voltage
Current drain 2...18 mA
Power consumption/input 0.9 W
Table 5.2.3.-6 Non-trip output SO1
Rated voltage 250 V AC/DC
Continuous carry 5 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time constant
L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load 100 mA at 24 V AC/DC
Table 5.2.3.-7 Non-trip output SO2 and IRF output
Rated voltage 250 V AC/DC
Continuous carry 5 A
Make and carry for 3.0 s 10 A
Make and carry for 0.5 s 15 A
Breaking capacity when the control-circuit time constant
L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load 100 mA at 24 V AC/DC
120
REM 610REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version