Description Parameter
(channel 0)
Setting range Default
setting
Customer’s
setting
Sensor/thermistor selection
for input RTD4
V124 0 = not in use
1 = Pt100 -45...
+150°C
2 = Pt250 -45...
+150°C
3 = Pt1000 -45...
+150°C
4 = Ni100 -45...
+250°C
5 = Ni120 -45...
+250°C
6 = Cu10 -45...
+150°C
7 = Ni120US -45...
+250°C
8 = PTC 0...20 kΩ
0
Sensor selection for input
RTD5
V125 0 = not in use
1 = Pt100 -45...
+150°C
2 = Pt250 -45...
+150°C
3 = Pt1000 -45...
+150°C
4 = Ni100 -45...
+250°C
5 = Ni120 -45...
+250°C
6 = Cu10 -45...
+150°C
7 = Ni120US -45...
+250°C
0
Sensor selection for input
RTD6
V126 0 = not in use
1 = Pt100 -45...
+150°C
2 = Pt250 -45...
+150°C
3 = Pt1000 -45...
+150°C
4 = Ni100 -45...
+250°C
5 = Ni120 -45...
+250°C
6 = Cu10 -45...
+150°C
7 = Ni120US -45...
+250°C
Remote control of settings V150 0 = setting group 1
1 = setting group 2
0
Unit address of the relay V200 1...254 1
Data transfer rate (SPA),
kbps
V201 9.6/4.8 9.6
152
REM 610REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537