Switching between group 1 and group 2 is accomplished by means of a digital
input
Switching between setting groups through group selection has higher
priority than through group configuration.
The setting values can be altered via the HMI or with a PC provided with the Relay
Setting Tool.
Before the relay is connected to a system it must be assured that the relay has been
given the correct settings. If there is any doubt, the setting values should be read
with the relay trip circuits disconnected or tested with current injection; refer to
section Check lists for additional information.
Table 5.1.4.12.-1 Setting values
Setting Description Setting range Default setting
FLA SEC. FLA secondary scaling factor 0.50...2.50
a)
1
t
6x
Safe stall time 2...120 s
b)
2s
p Weighting factor 20...100% 50 %
K
c
Time constant dial 1...64 1
49 ALARM Prior alarm level 50...100% 95%
49 RESTDIS Restart disable level 20...80% 40%
T
amb
Ambient temperature 0...70°C 40°C
48/14 PICKUP/FLA Start-up current for motor or
pickup value of element 48/14
1.0010.0 x FLA 1.00 x FLA
48/14 TDLY Start-up time for motor or
operate time of element 48/14
0.30...80.0 s 0.30 s
50P/FLA Pickup value of element 50P 0.50...20.0 x FLA 1.00 x FLA
50P TDLY Operate time of element 50P 0.05...30.0 s 0.05 s
51N/ I
n
CT Pickup value of element 51N 1.0...100% I
n
CT 1.0% I
n
CT
51N TDLY Operate time of element 51N 0.05...300 s 0.05 s
37/ FLA Pickup value of element 37 30...80% FLA 50% FLA
37 TDLY Operate time of element 37 2...600 s 2 s
46 PICKUP/ FLA Pickup value of element 46 0.100.50 x FLA 0.20 x FLA
46 TDIAL Time constant of element 46 at
IDMT characteristic
5...100 5
66 Restart disable value 5...500 s 5 s
66 COOL/Δt Countdown rate of start-up
time counter
2...250 s/h 2 s/h
Trip Fail Operate time of CBFAIL 0.10...60.0 s 0.10 s
RTD1A Alarm value RTD1A 0...200°C 0°C
RTD1A TDLY Operate time RTD1A TDLY 1...100 s 1 s
RTD1T Trip value RTD1T 0...200°C 0°C
RTD1T TDLY Operate time RTD1T TDLY 1...100 s 1 s
48
REM 610REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537