Setting Description Setting range Default setting
RTD2A Alarm value RTD2A 0...200°C 0°C
RTD2A TDLY Operate time RTD2A TDLY 1...100 s 1 s
RTD2T Trip value RTD2T 0...200°C 0°C
RTD2T TDLY Operate time RTD2T TDLY 1...100 s 1 s
RTD3A Alarm value RTD3A 0...200°C 0°C
RTD3A TDLY Operate time RTD3A TDLY 1...100 s 1 s
RTD3T Trip value RTD3T 0...200°C 0°C
RTD3T TDLY Operate time RTD3T TDLY 1...100 s 1 s
RTD4A Alarm value RTD4A 0...200°C 0°C
RTD14A TDLY Operate time RTD14A TDLY 1...100 s 1 s
RTD4T Trip value RTD4T 0...200°C 0°C
RTD4T TDLY Operate time RTD4T TDLY 1...100 s 1 s
RTD5A Alarm value RTD5A 0...200°C 0°C
RTD5A TDLY Operate time RTD5A TDLY 1...100 s 1 s
RTD5T Trip value RTD5T 0...200°C 0°C
RTD5T TDLY Operate time RTD5T TDLY 1...100 s 1 s
RTD6A Alarm value RTD6A 0...200°C 0°C
RTD6A TDLY Operate time RTD6A TDLY 1...100 s 1 s
RTD6T Trip value RTD6T 0...200°C 0°C
RTD6T TDLY Operate time RTD6T TDLY 1...100 s 1 s
PTC1 Trip value PTC1 0.1...15.0 kΩ 0.1 kΩ
PTC2 Trip value PTC2 0.1...15.0 kΩ 0.1 kΩ
a)
The FLA secondary scaling factor has only one setting and thus switching between setting groups does not apply.
b)
The setting step is 0.5.
Switchgroups and parameter masks
The settings can be altered and the functions of the relay selected in the SG_ selector
switchgroups. The switchgroups are software based and thus not physical switches
to be found in the hardware of the relay.
A checksum is used for verifying that the switches have been properly set. The
figure below shows an example of manual checksum calculation.
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610REM 610
1MRS755537