Table 5.1.4.12.-4 SGF3
Switch Function Default setting
SGF3/1 Disable of element 50P 0
SGF3/2 Disable of element 37 1
SGF3/3 Disable of element 51N 0
SGF3/4 Disable of element 46 0
SGF3/5 Disable of element 46R 0
*
When the switch is in position 1, the element is disabled.
SGF3/6 Start-up supervision
*
0 = based on thermal stress calculation
*
1 = based on definite-time overcurrent protection
0
SGF3/7 Pickup criteria for element (48/14 PICKUP)
2
x (48/14 TDLY)
*
0 = theelement will pickup when the conditions for motor start
up are met
*
1 = theelement will pickup when one or several phase currents
exceed the set pickup value
0
SGF3/8 Automatic doubling of the pickup value of element 50P
*
When the switch is in position 1, the set pickup value of
theelement will automatically be doubled at high inrush
situations
0
ΣSGF3 2
Table 5.1.4.12.-5 SGF4
Switch Function Default setting
SGF4/1 and SGF4/2 Disable of element 51N when one or several phase currents
exceed the FLA of the motor
00
SGF4/1 SGF4/2
x4 1 0
x6 0 1
x8 1 1
SGF4/3 Selection of ambient temperature
*
0 = set ambient temperature
*
1 = ambient temperature from RTD6
If the RTD module has not been installed, the set ambient
temperature will be used.
0
ΣSGF4 0
Table 5.1.4.12.-6 SGF5
Switch Function Default setting
SGF5/1 Selection of the latching feature for programmable LED1 0
SGF5/2 Selection of the latching feature for programmable LED2 0
SGF5/3 Selection of the latching feature for programmable LED3 0
SGF5/4 Selection of the latching feature for programmable LED4 0
SGF5/5 Selection of the latching feature for programmable LED5 0
SGF5/6 Selection of the latching feature for programmable LED6 0
SGF5/7 Selection of the latching feature for programmable LED7 0
52
REM 610REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537