Switch Function Default setting
SGF5/8 Selection of the latching feature for programmable LED8 0
*
When the switch is in position 0 and the signal routed to the
LED is reset, the programmable LED will be cleared.
*
When the switch is in position 1, the programmable LED will
remain lit although the signal routed to the LED is reset.
A latched programmable LED can be cleared either via the HMI,
a digital input or the serial bus.
ΣSGF5 0
SGB1...SGB5
The DI1 signal is routed to the functions below with the switches of switchgroup
SGB1, the DI2 signal with those of SGB2, and so forth.
Table 5.1.4.12.-7 SGB1...SGB5
Switch Function Default setting
SGB1...5/1
*
0 = targets are not cleared by the digital input signal
*
1 = targets are cleared by the digital input signal
0
SGB1...5/2
*
0 = targets are not cleared and latched output contacts are not
unlatched by the digital input signal
*
1 = targets are cleared and latched output contacts are
unlatched by the digital input signal
0
SGB1...5/3
*
0 = targets and memorized values are not cleared and latched
output contacts are not unlatched by the digital input signal
*
1 = targets and memorized values are cleared and latched
output contacts are unlatched by the digital input signal
0
SGB1...5/4 Switching between setting groups 1 and 2 using the digital input
*
0 = the setting group cannot be changed using the digital input
*
1 = the setting group is changed by using the digital input.
When the digital input is energized, setting group 2 will be
activated, if not, setting group 1 will be activated.
When SGB1...5/4 is set to 1, it is important that the
switch has the same setting in both setting
groups.
0
SGB1...5/5 External tripping by the digital input signal 0
SGB1...5/6 External triggering of the CBFAIL by the digital input signal 0
SGB1...5/7 External restart disable by the digital input signal 0
SGB1...5/8 Activating the emergency start by the digital input signal 0
SGB1...5/9 Blocking of element (48/14 PICKUP)
2
x (48/14 TDLY) or 48/14 by
the digital input signal (speed switch input)
0
SGB1...5/10 Blocking of element 50P by the digital input signal 0
SGB1...5/11 Blocking of element 37 by the digital input signal 0
SGB1...5/12 Blocking of element 51N by the digital input signal 0
SGB1...5/13 Blocking of element 46 by the digital input signal 0
SGB1...5/14 Time synchronization by the digital input signal 0
ΣSGB1...5 0