73
Event reason
Event code
Configuration set 1
Configuration set 2
Function type
Information number
GI
Relative time
Type identification
51N Pickup/Reset 1E27/
1E28
X X 160 67 X 1E27 2
51N Trip/Reset 1E29/
1E30
X X 160 92 - 1E27 2
46 Pickup/Reset 1E31/
1E32
X X 21 84 X 1E31 2
46 Trip/Reset 1E33/
1E34
X X 21 90 - 1E31 2
46R Trip/Reset 1E35/
1E36
X X 22 90 - 1E1 2
CBFAIL Activated/Reset 1E37/
1E38
X X 160 85 - - 1
PO1 Activated/Reset 2E1/
2E2
X X 251 27 X - 1
PO2 Activated/Reset 2E3/
2E4
X X 251 28 X - 1
PO3 Activated/Reset 2E5/
2E6
X X 251 29 X - 1
SO1 Activated/Reset 2E7/
2E8
X X 251 30 X - 1
SO2 Activated/Reset 2E9/
2E10
X X 251 31 X - 1
DI1 Activated/Deactivated 2E11/
2E12
X X 249 231 X - 1
DI2 Activated/Deactivated 2E13/
2E14
X X 249 232 X - 1
DI3 Activated/Deactivated 2E15/
2E16
- X 249 233 X - 1
DI4 Activated/Deactivated 2E17/
2E18
- X 249 234 X - 1
DI5 Activated/Deactivated 2E19/
2E20
- X 249 235 X - 1
49/38-1 Alarm/Reset 2E21/
2E22
- X 210 11 X 2E21 2
49/38-1 Trip/Reset 2E23/
2E24
- X 210 21 - 2E23 2
49/38-2 Alarm/Reset 2E25/
2E26
- X 211 11 X 2E25 2
49/38-2 Trip/Reset 2E27/
2E28
X 211 21 - 2E27 2
a)
) When start-up supervision based on thermal stress calculation has been selected (SGF3/6=0), the function type in brackets will be used.
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610REM 610
1MRS755537