Table 5.1.14.1.-5 Mapping of Modbus data: user-defined registers
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
UDR 1 1 or 385
UDR 2 2 or 386
UDR 3 3 or 387
UDR 4 4 or 388
UDR 5 5 or 389
UDR 6 6 or 390
UDR 7 7 or 391
UDR 8 8 or 392
UDR 9 9 or 393
UDR 10 10 or 394
UDR 11 11 or 395
UDR 12 12 or 396
UDR 13 13 or 397
UDR 14 14 or 398
UDR 15 15 or 399
UDR 16 16 or 400
Table 5.1.14.1.-6 Mapping of Modbus data: status registers
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Status register 1 401 IRF code See Structure 1
Status register 2 402 Warning
codes
See Structure 1
Status register 3 403 See Structure 1
Table 5.1.14.1.-7 Mapping of Modbus data: analog data
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Phase current I
a
xI
n
(CT) 404 0...5000 0...50 x FLA
Phase current I
b
xI
n
(CT) 405 0...5000 0...50 x FLA
Phase current I
c
xI
n
(CT) 406 0...5000 0...50 x FLA
Ground-fault current x I
n
(CT) 407 0...8000 0...800.0% I
n
(CT)
NPS current 408 0...5000 0...50 x FLA
Temperature from RTD1 409 -40...999 °C (signed)
a)
Temperature from RTD2 410 -40...999 °C (signed)
a)
Temperature from RTD3 411 -40...999 °C (signed)
a)
Temperature from RTD4 412 -40...999 °C (signed)
a)
Temperature from RTD5 413 -40...999 °C (signed)
a)
Temperature from RTD6 414 -40...999 °C (signed)
a)
Thermistor 1, resistance value 415 0...200 0...20.0 kΩ
b)
Thermistor 2, resistance value 416 0...200 0...20.0 kΩ
b)
82
REM 610REM 610
Motor Protection Relay