87
Table 5.1.14.1.-14 Fault record
Address Signal name Range Comment
601 Latest selection code
a)
1...2 1 = read oldest unread record
2 = read oldest stored record
602 Sequence number 1...999
603 Unread records left 0...6
604 Time stamp of the recorded data, date 2 bytes: YY.MM
605 Time stamp of the recorded data, time 2 bytes: DD.HH
606 Time stamp of the recorded data, date and time 2 bytes: MM.SS
607 Time stamp of the recorded data, time 0...999 0...999 ms
608 Phase current I
a
0...5000 0...50 x FLA
609 Phase current I
b
0...5000 0...50 x FLA
610 Phase current I
c
0...5000 0...50 x FLA
611 Ground-fault current 0...8000 0...800.0%
612 NPS current 0...5000 0...50 x FLA
613 Thermal stress value 0...100 0...100%
614 Number of motor start ups 0...999 0...999
615 Thermal level at start 0...106 0...106%
616 Thermal level at end 0...106 0...106%
617 Temperature from RTD1 -40...999 -40...999°C
b)
618 Temperature from RTD2 -40...999 -40...999°C
b)
619 Temperature from RTD3 -40...999 -40...999°C
b)
620 Temperature from RTD4 -40...999 -40...999°C
b)
621 Temperature from RTD5 -40...999 -40...999°C
b)
622 Temperature from RTD6 -40...999 -40...999°C
b)
623 Thermistor 1, resistance value 0...200 0...20 kΩ
c)
624 Thermistor 2, resistance value 0...200 0...20 kΩ
c)
625 Pickup duration of element 49/38-1, alarm 0...100 0...100%
626 Pickup duration of element 49/38-1, trip 0...100 0...100%
627 Pickup duration of element 49/38-2, alarm 0...100 0...100%
628 Pickup duration of element 49/38-2, trip 0...100 0...100%
629 Pickup duration, element (48/14 PICKUP)
2
x (48/14
TDLY) or 48/14
0...100 0...100%
630 Pickup duration, element 50P-1 0...100 0...100%
631 Pickup duration, element 46 0...100 0...100%
632 Pickup duration, element 51N 0...100 0...100%
633 Pickup duration, element 37 0...100 0...100%
a)
Readable and writeable register.
b)
If the input is out of operation or the optional RTD module has not been installed, the value -32768 will be returned.
c)
If the input is out of operation or the optional RTD module has not been installed, the value 655 will be returned.
Structure 3
This structure contains Modbus event records. Refer to Event records earlier in this
section for the reading method.