Table 5.1.14.1.-15 Event record
Address Signal name Range Comment
671 Latest selection code
a)
1...3 1 = read oldest unread record
2 = read oldest stored record
3 = clear Modbus event buffer
-1...-99 -1...-99 = move to the nth
newest record
672 Sequence number 1...999
673 Unread records left 0...99
674 Time stamp of the event, date 2 bytes: YY.MM
675 Time stamp of the event, date and time 2 bytes: DD.HH
676 Time stamp of the event, time 2 bytes: MM.SS
677 Time stamp of the event, time 0...999 0...999 ms
678 Event data See Table 5.1.14.1.-16 for
Modbus DI-point events and
Table 5.1.14.1.-17 for
informative events
679
a)
Readable and writeable register.
Table 5.1.14.1.-16 Modbus DI-point event
Address Name Range Comment
678 0 Modbus DI-point 1...99 MSB = 0
679 Modbus DI value 0...1
Table 5.1.14.1.-17 Informative event
Address Name Range Comment
678 1 SPA channel 0...3 MSB = 1
679 SPA event 0...63
Structure 4
The relay's real-time clock is stored in this structure. It can be updated by presetting
the whole register structure in one Modbus transaction.
Table 5.1.14.1.-18 Real-time clock structure
Address Description Range
721 Year 0...99
722 Month 1...12
723 Day 1...31
724 Hour 0...23
725 Minute 0...59
726 Second 0...59
727 Hundredth of a second 0...99
88
REM 610REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537