Variable Actual
settings (R),
channel 0
Group/
Channel 1 (R,
W, P)
Group/
Channel 2 (R,
W, P)
Setting range
Pickup value of element
46
S15
b)
1S15 2S15 0.100.50 x
FLA
Time constant of element
46
S16 1S16 2S16 5...100
Restart disable value S17 1S17 2S17 5...500 s
Countdown rate of start-
up time counter
S18 1S18 2S18 2...250 s/h
Operate time of CBFAIL S19 1S19 2S19 0.10...60.0 s
Alarm value RTD1A S20
b)
1S20 2S20 0...200°C
Operate time RTD1A
TDLY
S26 1S26 2S26 1...100 s
Trip value RTD1T S32
b)
1S32 2S32 0...200°C
Operate time RTD1T
TDLY
S38 1S38 2S38 1...100 s
Alarm value RTD2A S21
b)
1S21 2S21 0...200°C
Operate time RTD2A
TDLY
S27 1S27 2S27 1...100 s
Trip value RTD2T S33
b)
1S33 2S33 0...200°C
Operate time RTD2T
TDLY
S39 1S39 2S39 1...100 s
Alarm value RTD3A S22
b)
1S22 2S22 0...200°C
Operate time RTD3A
TDLY
S28 1S28 2S28 1...100 s
Trip value RTD3T S34
b)
1S34 2S34 0...200°C
Operate time RTD3T
TDLY
S40 1S40 2S40 1...100 s
Alarm value RTD4A S23
b)
1S23 2S23 0...200°C
Operate time RTD4A
TDLY
S29 1S29 2S29 1...100 s
Trip value RTD4T S35
b)
1S35 2S35 0...200°C
Operate time RTD4T
TDLY
S41 1S41 2S41 1...100 s
Alarm value RTD5A S24
b)
1S24 2S24 0...200°C
Operate time RTD5A
TDLY
S30 1S30 2S30 1...100 s
Trip value RTD5T S36
b)
1S36 2S36 0...200°C
Operate time RTD5T
TDLY
S42 1S42 2S21 1...100 s
Alarm value RTD6A S25
b)
1S25 2S25 0...200°C
Operate time RTD6A
TDLY
S31 1S31 2S31 1...100 s
Trip value RTD6T S37
b)
1S37 2S37 0...200°C
Operate time RTD6T
TDLY
S43 1S43 2S43 1...100 s
Trip value PTC1 S44
b)
1S44 2S44 0.1...15.0 kΩ
Trip value PTC2 S45
b)
1S45 2S45 0.1...15.0 kΩ
90
REM 610REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version