91
Variable Actual
settings (R),
channel 0
Group/
Channel 1 (R,
W, P)
Group/
Channel 2 (R,
W, P)
Setting range
Checksum, SGF 1 S61 1S61 2S61 0...255
Checksum, SGF 2 S62 1S62 2S62 0...255
Checksum, SGF 3 S63 1S63 2S63 0...255
Checksum, SGF 4 S64 1S64 2S64 0...7
Checksum, SGF 5 S65 1S65 2S65 0...255
Checksum, SGB 1 S71 1S71 2S71 0...16383
Checksum, SGB 2 S72 1S72 2S72 0...16383
Checksum, SGB 3 S73
c)
1S73 2S73 0...16383
Checksum, SGB 4 S74
c)
1S74 2S74 0...16383
Checksum, SGB 5 S75
c)
1S75 2S75 0...16383
Checksum, SGR 1 S81 1S81 2S81 0...524287
Checksum, SGR 2 S82 1S82 2S82 0...524287
Checksum, SGR 3 S83 1S83 2S83 0...524287
Checksum, SGR 4 S84 1S84 2S84 0...524287
Checksum, SGR 5 S85 1S85 2S85 0...524287
Checksum, SGL 1 S91 1S91 2S91 0...4194303
Checksum, SGL 2 S92 1S92 2S92 0...4194303
Checksum, SGL 3 S93 1S93 2S93 0...4194303
Checksum, SGL 4 S94 1S94 2S94 0...4194303
Checksum, SGL 5 S95 1S95 2S95 0...4194303
Checksum, SGL 6 S96 1S96 2S96 0...4194303
Checksum, SGL 7 S97 1S97 2S97 0...4194303
Checksum, SGL 8 S98 1S98 2S98 0...4194303
a)
The setting step is 0.5.
b)
If the protection element is out of operation, the number indicating the currently used value will be
displaced by “999” when parameters are read via the SPA bus and by dashes on the LCD.
c)
If the optional RTD module has not been installed, dashes will be shown on the LCD and “99999” when
the parameter is read via the SPA bus.
Recorded data
Parameter V1 shows the element and phase which caused the trip. Parameter V2
shows the trip target code.
Parameter V3 the start-up time of the latest motor start up and parameters V4...V8
show the number of pickups of the protection elements.
Table 5.1.15.-2 Recorded data: Channel 0
Recorded data Parameter
(R)
Value
Element/phase which caused the
trip
V1 1= (48/14 PICKUP)
2
x (48/14 TDLY) or 48/
14 I
c
2=(48/14 PICKUP)
2
x (48/14 TDLY) or 48/
14 I
b
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610REM 610
1MRS755537