93
Recorded data Parameter
(R)
Value
Number of pickups of element (48/
14 PICKUP)2 x (48/14 TDLY) or
48/14
V4 0...999
Number of pickups of element 50P V5 0...999
Number of pickups of element 51N V6 0...999
Number of pickups of element 37 V7 0...999
Number of pickups of element 46 V8 0...999
The last five recorded values can be read with parameters V1...V28 on channels
1...5. Event n denotes the last recorded value, n-1 the next one, and so forth.
Table 5.1.15.-3 Recorded data: Channels 1...5
Recorded data Event (R) Value
n
Channel 1
n-1
Channel 2
n-2
Channel 3
n-3
Channel 4
n-4
Channel 5
Phase current I
a
1V1 2V1 3V1 4V1 5V1 0...50 x FLA
Phase current I
b
1V2 2V2 3V2 4V2 5V2 0...50 x FLA
Phase current I
b
1V3 2V3 3V3 4V3 5V3 0...50 x FLA
Ground-fault
current
1V4 2V4 3V4 4V4 5V4 0...800% I
n
CT
NPS current 1V5 2V5 3V5 4V5 5V5 0...50 x FLA
Thermal stress
value
1V6 2V6 3V6 4V6 5V6 0...100%
Number of
motor start ups
1V7 2V7 3V7 4V7 5V7 0...999
Thermal level at
start
1V8 2V8 3V8 4V8 5V8 0...106%
Thermal level at
end
1V9 2V9 3V9 4V9 5V9 0...106%
Temperature
from RTD1
1V10 2V10 3V10 4V10 5V10 -40...+999°C
Temperature
from RTD2
1V11 2V11 3V11 4V11 5V11 -40...+999°C
Temperature
from RTD3
1V12 2V12 3V12 4V12 5V12 -40...+999°C
Temperature
from RTD4
1V13 2V13 3V13 4V13 5V13 -40...+999°C
Temperature
from RTD5
1V14 2V14 3V14 4V14 5V14 -40...+999°C
Temperature
from RTD6
1V15 2V15 3V15 4V15 5V15 -40...+999°C
Thermistor1,
resistance value
1V16 2V16 3V16 4V16 5V16 0...20 kΩ
Thermistor2,
resistance value
1V17 2V17 3V17 4V17 5V17 0...20 kΩ
Pickup duration
of element 49/
38-1, alarm
1V18 2V18 3V18 4V18 5V18 0...100%
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610REM 610