Recorded data Event (R) Value
n
Channel 1
n-1
Channel 2
n-2
Channel 3
n-3
Channel 4
n-4
Channel 5
Pickup duration
of element 49/
38-1, trip
1V19 2V19 3V19 4V19 5V19 0...100%
Pickup duration
of element 49/
38-2, alarm
1V20 2V20 3V20 4V20 5V20 0...100%
Pickup duration
of element 49/
38-2, trip
1V21 2V21 3V21 4V21 5V21 0...100%
Pickup duration,
element (48/14
PICKUP)
2
x (48/
14 TDLY) or 48/
14
1V22 2V22 3V22 4V22 5V22 0...100%
Pickup duration,
element 50P
1V23 2V23 3V23 4V23 5V23 0...100%
Pickup duration,
element 46
1V24 2V24 3V24 4V24 5V24 0...100%
Pickup duration,
element 51N
1V25 2V25 3V25 4V25 5V25 0...100%
Pickup duration,
element 37
1V26 2V26 3V26 4V26 5V26 0...100%
Time stamp of
the recorded
data, date
1V27 2V27 3V27 4V27 5V27 YY-MM-DD
Time stamp of
the recorded
data, time
1V28 2V28 3V28 4V28 5V28 HH.MM; SS.sss
Disturbance recorder
Table 5.1.15.-4 Parameters for the disturbance recorder
Description Parameter (channel 0) R, W Value
Remote triggering M1
a)
W1
Clear recorder memory M2 W 1
Sampling rate M15
b)
R, W 800/960 Hz
400/480 Hz
50/60 Hz
Station identification/unit number M18 R, W 0...9999
Rated frequency M19 R 50 or 60 Hz
Name of the motor drive M20 R, W Max 16 characters
Digital channel texts M40...M47 R -
Analog channel texts M60...M63 R -
Analog channel conversion factor and unit
for I
a
,I
b
and I
c
M80
c)d)
R, W Factor 0...65535, unit (A,
kA), e.g. 10,kA
M81 and R
M82 R
94
REM 610REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version