Event Weighting factor Default value of
triggering mask,
V236
Default value of
triggering edge,
V237
Default value of
storing mask,
V238
Trip of element
37
128 1 0 1
Pickup of
element 51N
256 0 0 0
Trip of element
51N
512 1 0 1
Pickup of
element 46
1024 0 0 0
Trip of element
46
2048 1 0 1
Motor start up 4096 0 0 1
Σ 2728 0 6842
a)
0 = rising edge, 1 = falling edge.
Table 5.1.15.-6 Disturbance recorder external triggering and storing
Event Weighting factor Default value of
triggering mask,
V241
Default value of
triggering edge,
V242
a)
Default value of
storing mask,
V243
DI11000
DI22000
DI34000
DI48000
DI5 16 0 0 0
Σ 000
a)
0 = rising edge; 1 = falling edge.
Table 5.1.15.-7 Control parameters
Description Parameter R, W, P Value
Reading of the event buffer L R Time, channel number and event code
Re-reading of the event buffer B R Time, channel number and event code
Reading of relay state data C R 0 = Normal state
1 = The relay has been subject to an
automatic reset
2 = Overflow of the event buffer
3 = Both 1 and 2
Resetting of relay state data C W 0 = Reset E50 and E51
1 = Reset only E50
2 = Reset only E51
4 = Reset all events including E51 except for
E50
Time reading and setting T R, W SS.sss
Date and time reading and setting D R, W YY-MM-DD HH.MM;SS.sss
Type designation of the relay F R REM 610
Unlatching output contacts V101 W 1 = Unlatch
Clearing targets and memorized values and
unlatching contacts (master reset)
V102 W 1 = Clear and unlatch
FLA secondary (protected unit scaling factor) V103 R, W (P) 0.50...2.50