97
Description Parameter R, W, P Value
Rated frequency V104 R, W (P) 50 or 60 Hz
Time setting range for demand values in
minutes
V105 R, W 0...999 min
Non-volatile memory settings V106 R, W 0...63
Time setting for disabling new trip targets on the
LCD
V108 R, W (P) 0...999 min
Activating the self-supervision V109 W (P) 1 = Self-supervision output contact is
activated and the READY target LED starts
to flash
0 = Normal operation
LED test for pickup and trip targets V110 W (P) 0 = Pickup and trip LEDs off
1 = Trip LED on, pickup LED off
2 = Pickup LED on, trip LED off
3 = and trip LEDs on
LED test for programmable LEDs V111 W (P) 0...255
Trip-circuit supervision V113 R, W 0 = Not in use
1 = In use
Store counter
a)
V114 R 0...65535
Sensor/thermistor selection for input RTD1 V121
b)
R, W (P) 0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
8 = PTC 0...20 kΩ
Sensor selection for input RTD2 V122
b)
R, W (P) 0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
Sensor selection for input RTD3 V123
b)
R, W (P) 0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
Sensor/thermistor selection for input RTD4 V124
b)
R, W (P) 0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
8 = PTC 0...20 kΩ
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610REM 610
1MRS755537