Description Parameter R, W, P Value
Sensor selection for input RTD5 V125
b)
R, W (P) 0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
Sensor selection for input RTD6 V126
b)
R, W (P) 0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
Remote control of setting group V150 R, W 0 = Setting group 1
1 = Setting group 2
Entering the SPA password for settings V160 W 1...999
Changing the SPA password or taking the
password protection into use
V161 W (P) 1...999
Changing the HMI Setting password V162 W 1...999
Changing the HMI Communication password V163 W 1...999
Clearing trip counters or AR counter V166 W (P) 1 = Clear trip counters
2 = Clear AR counters
Restoring factory settings V167 W (P) 2 = Restore factory settings for CPU
3 = Restore factory settings for
4 = Restore factory settings for CPU and
RTD
Warning code V168 R 0...63
c)
IRF code V169 R 0...255
c)
Unit address of the relay V200 R, W 1...254
Data transfer rate (SPA), kbps V201 R, W 9.6/4.8
Rear communication V202 W 1 = Rear connector activated
Rear communication protocol V203 R, W 0 = SPA
1 = IEC_103
2 = Modbus RTU
3 = Modbus ASCII
Connection type V204 R, W 0 = Loop
1 = Star
Line-idle state V205 R, W 0 = Light off
1 = Light on
Optional communication module V206 R, W (P) 0 = Not in use
1 = In use
d)
HMI language set information V226 R 00...99
CPU software number V227 R 1MRS118511
CPU software revision V228 R A...Z
CPU build number V229 R XXX
RTD software number 1V227 R 1MRS118514
RTD software revision 1V228 R A...Z
98
REM 610REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537