19. Technical data
Table 7. Power supply
Description Type 1 Type 2
V nominal (V
n
) 100, 110, 120, 220, 240 V AC,
60 and 50 Hz
48, 60, 110, 125, 220, 250 V DC
24, 30, 48, 60 V DC
V
n
variation 38...110% of V
n
(38...264 V AC)
80...120% of V
n
(38.4...300 V DC)
50...120% of V
n
(12...72 V DC)
Start-up threshold 19.2 V DC
(24 V DC * 80%)
Burden of auxiliary voltage supply
under quiescent (Pq)/operating
condition
250 V DC ~8.5 W (nominal) / ~14.1
W (maximum) 240 V AC ~10.2 W
(nominal) / ~16.1 W (maximum)
60 V DC ~6.7 W (nomi-
nal) / ~12.9 W (maxi-
mum)
Ripple in the DC auxiliary voltage Max 12% of the DC value (at frequency of 100 Hz)
Maximum interruption time in the
auxiliary DC voltage without
resetting the relay
110 V DC: 84 ms 110 V AC: 116
ms
48 V DC: 68 ms
Fuse type T4A/250 V
Table 6. Dimensions
Description Value
Width frame 7.08” (179.8 mm)
case 6.46” (164 mm)
Height frame 6.97 (177 mm), 4U
case 6.30” (160 mm)
Depth case 7.64” (194 mm)
Weight relay 7.72 lbs. (3.5 kg)
draw-out unit 3.97 lbs. (1.8 kg)