EasyManua.ls Logo

ABB REM615 ANSI - Page 16

ABB REM615 ANSI
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB 16
1MAC251744 -PG Rev. A
Issued: 03.01.2010
Motor Protection
REM615 ANSI
Product Version 2.0
Table 12. Self-diagnostics alarm signal output (SO) [Typical operation time: 5...8 ms]
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 15 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load 100 mA at 24 V AC/DC
Table 13. Double-pole power output (PO) relays with TCM [Typical operation time: 8...11 ms]
Rated voltage
250 V AC/DC
Continuous contact carry 8 A
Make and carry for 3.0 s 15 A
Make and carry 0.5 s 30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC (two
contacts connected in series)
5 A/3 A/1 A
Minimum contact load 100 mA at 24 V AC/DC
Trip-circuit monitoring (TCM):
• Control voltage range
• Current drain through the monitoring circuit
• Minimum voltage over the TCM contact
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
Table 14. Single-pole power output (PO) relays [Typical operation time: 8...11 ms]
Description
Va l u e
Rated voltage
250 V AC/DC
Continuous contact carry 8 A
Make and carry for 3.0 s 15 A
Make and carry 0.5 s 30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
5 A/3 A/1 A
Minimum contact load 100 mA at 24 V AC/DC
Table 15. Lens sensor and optic  ber for arc  ash detection (AFD)
Description
Va l u e
Fibre-optic cable including lens
1.5 m, 3.0 m or 5.0 m
Normal service temperature range of the lens -40° to +212° F (-40° to 100° C)
Maximum service temperature range of the lens, max 1 h +284° F (+140° C)
Minimum permissible bending radius of the
connection  bre
3.94” (100 mm)

Related product manuals