ABB 24
1MAC251744 -PG Rev. A
Issued: 03.01.2010
Motor Protection
REM615 ANSI
Product Version 2.0
Table 33. 
ree-phase overvoltage protection (59) main settings
Parameter Function Value (Range) Step
Pickup range 59 0.05...1.60 x U
n
0.01
Time multiplier 59 0.05...15.00 0.05
De nite time delay 59 40...300000 ms 10
Operating curve type
1)
59 De nite or inverse time
Curve type: 5, 15, 17, 18, 19, 20
1)
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
Table 34.  ree-phase undervoltage protection (27)
Characteristic Value
Pickup
accuracy
Depending on the frequency of the voltage
measured: f
n
±2Hz
±1.5% of the set value or ±0.002 x U
n
Pickup time
1) 2)
U
Fault
= 0.9 x set Pickup range Minimum Typical Maximum
62 ms 64 ms 66 ms
Reset time < 40 ms
Reset ratio Depends on the set Relative hysteresis
Retardation time < 35 ms
Trip time accuracy in de nite time mode ±1.0% of the set value or ±20 ms
Trip time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics DFT: -50dB at f = n x f
n
,
where n = 2, 3, 4, 5,…
Table 35.  ree-phase undervoltage protection (27) main settings
Parameter Function Value (Range) Step
Pickup range 27 0.05...1.20 x U
n
0.01
Time multiplier 27 0.05...15.00 0.05
De nite time delay 27 60...300000 ms 10
Operating curve type
1)
27 De nite or inverse time
Curve type: 5, 15, 21, 22, 23
1)
Pickup range = 1.0 x U
n
, Voltage before fault 1.1 x U
n
, f
n
= 50 Hz, undervoltage in one phase-to-phase with nominal frequence injected from
random phase angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Minimum Pickup range = 0.50, Pickup range multiples in range of 0.90 to 0.20
1)
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter

Related product manuals