EasyManua.ls Logo

ABB REM615 ANSI - Page 31

ABB REM615 ANSI
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB 31
Motor Protection
REM615 ANSI
Product Version 2.0
1MAC251744 -PG Rev. A
Issued: 03.01.2010
Table 60. 
ree-phase voltage measurements (VA, VB, VC)
Characteristic Value
Pickup
accuracy
Depending on the frequency of the voltage measured: fn ±2Hz
(at voltages in range 0.01...1.15 x Un)
±0.5% or ±0.002 x U
n
Suppression of har-
monics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…
RMS: No suppression
Table 61. Voltage sequence components (V1, V2, V0)
Characteristic Value
Pickup
accuracy
Depending on the frequency of the voltage measured: fn ±2Hz
at voltages in the range of 0.01…1.15 x Un
±1.0% or ±0.002 x U
n
Suppression of har-
monics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…
Table 64.  ree-phase power and energy (P, E)
Characteristic Value
Pickup
accuracy
At all three currents in range 0.10…1.20 x In
At all three voltages in range 0.50…1.15 x Un
At the frequency fn ±1Hz
Active power and energy in range |PF| > 0.71
Reactive power and energy in range |PF| < 0.71
±1.5% for power (S,P and Q)
±0.015 for power factor
±1.5% for energy
Suppression of har-
monics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…
Table 62. Ground current measurement (IG)
Characteristic Value
Pickup
accuracy
Depending on the frequency of the current measured: f/fn = ±2Hz
±0.5% or ±0.002 x In
at currents in the range of 0.01...4.00 x In
Suppression of har-
monics
DFT: -50dB at f = n x fn, where n = 2, 3, 4, 5,…
RMS: No suppression
Table 63. Ground voltage measurement (VG)
Characteristic Value
Pickup
accuracy
Depending on the frequency of the current measured: f/fn = ±2Hz
±0.5% or ±0.002 x Un
Suppression of har-
monics
DFT: -50dB at f = n x fn, where n = 2, 3, 4, 5,…
RMS: No suppression