Loading...
IEC15000436-1-en.vsdx
R
jX
RFPPFwZxR1FwRFPPRvZx
X1Fw
RFPPFwZxRFPPRvZx
RLd
80%
P1
P2
P3
P4
P5 P6
P7
P8
P9
ArgLd
ArgDir
ArgNegRes
(
)
(
)
IEC15000436 V1 EN-US
Figure 20: Proposed test points for phase-to-phase loop of measuring
element
Table 22: Test points for phase-to-phase loop measuring element
Test point
R X Comment
P1 0
X1Fw
P2
R1Fw X1Fw
P3 (0.8 ∗
R1Fw
) +
RFPPFwZx
0.8 ∗
X1Fw
P4 0.8 ∗
RFPPFwZx
0.8 ∗
RFPPFwZx
∗ tan
(
ArgLd
)
P5
RLd
0
P6
RFPPFwZx
0 If
LEModeZx
= Off and
OpLoadEnch
= Off
P7 0.5 ∗
RLd
0.5 ∗
RLd
∗ tan
(
ArgDir
)
P8 0.5 ∗
RFPPRvZx X1Fw
P9 0.8 ∗
X1Fw
∗ tan
(
ArgNegRes
)
0.8 ∗
X1Fw
1MRK 506 377-UEN C Section 10
Testing functionality by secondary injection
Railway application RER670 2.2 IEC 97