10.12.2 Liquid medium supervision SSIML
GUID-6426FDDA-B949-4FE7-BF42-B52014A9344B v4
Prepare the IED for verification of settings as outlined in section
"Preparing the
IED to verify settings" in this chapter.
Values of logical signals for SSIMG protection are available on the local HMI
under Main menu/Tests/Function status/Monitoring/InsulationLiquid(71)/
SSIML(71):x, where x = 1, 2,....4.
Check that the input logical signal BLOCK is logical zero and that on the local
HMI, the logical signals LVLALM, LVLLO, TEMPALM, TEMPLO, ALARM and
LOCKOUT are logical zero.
10.12.2.1 Testing the liquid medium supervision for level alarm and level
lockout conditions
GUID-C1F1E6CA-9512-4358-A4E7-84CC3698D156 v3
1. Connect the binary inputs to consider liquid level to initiate the alarms.
2. Consider the analogue level input SENLEVEL and set SENLEVEL to a value
lower than LevelAlmLimit or activate binary input signal SENLVLALM, check
that outputs LVLALM and ALARM are activated after a set time delay of
tLevelAlarm.
3. Liquid level lockout input SENLVLLO can be used to set LVLLO.
4. Also, reduce the liquid level input below LevelLOLimit or activate the binary
input signal SENLVLLO, check that LVLLO signal after a set time delay of
tLevelLockOut.
5. Activate BLOCK binary input and check that the outputs LVLALM, LVLLO,
ALARM and LOCKOUT disappears.
6. Reset the BLOCK binary input.
7. Make sure that level lockout condition exists and then activate the reset lock
out input RESETLO and check that the outputs PRESLO and LOCKOUT reset.
10.12.2.2 Testing the liquid medium supervision for temperature alarm and
temperature lock out conditions
GUID-189AF20B-D0E3-453D-A787-68F25D0903D3 v1
1. Consider the analogue temperature input SENTEMP and set SENTEMP to a
value higher than TempAlarmLimit, check that outputs TEMPALM and ALARM
are activated after a set time delay of tTempAlarm.
2. Temperature lockout input SETTLO can be used to set TEMPLO signal.
3. Also, increase further the temperature input above TempLOLimit, check that
the outputs TEMPLO and LOCKOUT appears after a set time delay of
tTempLockOut.
1MRK 506 377-UEN C Section 10
Testing functionality by secondary injection
Railway application RER670 2.2 IEC 165
Commissioning manual