Before starting any test, verify the following settings in PCM600 or the local HMI
for TR1ATCC, TR8ATCC and TCMYLTC and TCLYLTC.
Confirm power system base quantities I1Base, I2Base, UBase.
Main menu/Settings/IED Settings/Control/TransformerVoltageControl(ATCC,
90)/TR1ATCC:x/TR8ATCC:x/General
and
Main menu/Settings/IED Settings/Control/TransformerVoltageControl(ATCC,
90)/TR1ATCC:x
.
Confirm that the setting for short circuit impedance Xr2 for TR1ATCC or
TR8ATCC is in accordance with transformer data:
Short circuit impedance, available on the local HMI under Main menu/
Settings/IED settings/Control/TransformerVoltageControl(ATCC,
90)/TR1ATCC:x/TR8ATCC:x/Xr2.
Confirm that the setting for TCMYLTC or TCLYLTC is in accordance with
transformer data:
Tap change timeout duration - effectively the maximum transformer tap
change time, tTCTimeout, available on the local HMI under Main menu/
Settings/IED Settings/Control/TransformerTapControl(YLTC,84)/
TCMYLTC:x/TCLYLTC:x/tTCTimeout.
Load tap changer pulse duration - required length of pulse from IED to
load tap changer, tPulseDur, available on the local HMI under Main
menu/Settings/IED Settings/Control/TransformerTapControl(YLTC,
84)/TCMYLTC:x/TCLYLTC:x/tPulseDur.
Transformer tap range, LowVoltTap and HighVoltTap, available on the
local HMI under Main menu/Settings/IED Settings/Control/
TransformerTapControl(YLTC,84)/TCMYLTC:x/TCLYLTC:x/
HighVoltTap and .
Load tap changer code type - method for digital feedback of tap position,
CodeType, available on the local HMI under Main menu/Settings/ IED
settings/Control/TransformerTapControl(YLTC,84)/TCMYLTC:x/
TCLYLTC:x/CodeType.
During the installation and commissioning, the behavior of the
voltage control functions for different tests may be governed by a
parameter group, available on the local HMI under Main menu/
Settings/IED Settings/Control/
TransformerVoltageControl(ATCC,90)/TR1ATCC:x/
TR8ATCC:x. These parameter settings can cause a Total Block,
Automatic Block or Alarm for a variety of system conditions
including over and under voltage, over current and tap changer
failure. It is important to review these settings and confirm the
Section 10 1MRK 506 377-UEN C
Testing functionality by secondary injection
142 Railway application RER670 2.2 IEC
Commissioning manual