IEC15000433-2-en.vsd
RLd
jX
P1
P2
P3
P4
P5
P6
P7
P8
ArgLd
(
)
IEC15000433 V2 EN-US
Figure 17: Proposed test points for phase-to-earth loop of circular
characteristic in compensated/high impedance earthed systems
Table 19: Test points for phase-to-earth loop of circular characteristic for compensated/high
impedance earthed systems
Test point
R X Comment
P1
Z1CircleStart
/2 ∗
cos(
LineAng
)
Z1CircleStart
/2 ∗
sin(
LineAng
)
P2 0.8 ∗
Z1CircleStart
/2 ∗
cos(
ArgLd
)
0.8 ∗
Z1CircleStart
/2 ∗
sin(
ArgLd
)
If 2I0 <
I0MinOp
P3
RLd
/2 0 If 2I0 <
I0MinOp
P4 -
Z1CircleStart
/2 ∗
cos(
LineAng
)
-
Z1CircleStart
/2 ∗
sin(
LineAng
)
P5 -0.8 ∗
Z1CircleStart
/2
∗ cos(
ArgLd
)
-0.8 ∗
Z1CircleStart
/2
∗ sin(
ArgLd
)
If 2I0 <
I0MinOp
P6 -
RLd
/2 0 If 2I0 <
I0MinOp
P7
Z1CircleStart
/2 ∗
cos(
ArgLd
)
-
Z1CircleStart
/2 ∗
sin(
ArgLd
)
P8 -
Z1CircleStart
/2 ∗
cos(
ArgLd
)
Z1CircleStart
/2 ∗
sin(
ArgLd
)
Section 10 1MRK 506 377-UEN C
Testing functionality by secondary injection
90 Railway application RER670 2.2 IEC
Commissioning manual