2.3.5.6 LD0.RESVMMXU1 Residual voltage limit supervision
Table 27: LD0.RESVMMXU1 Residual voltage limit supervision
IEC 61850 name SA name Description Values
LD0.RESVMMXU1
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
2.3.6 Protection functions
2.3.6.1 LD0.LEDPTRC1 Global protection signals
Table 28: LD0.LEDPTRC1 Global protection signals
IEC 61850 name SA name Description Values
LD0.LEDPTRC1 Global protection signals
.Op.general - -General Operate 1=Operate
.Op.phsA - -phsA Operate 1=Operate
.Op.phsB - -phsB Operate 1=Operate
.Op.phsC - -phsC Operate 1=Operate
.Str.general - -General Start 1=Start
.Str.phsA - -phsA Start 1=Start
.Str.phsB - -phsB Start 1=Start
.Str.phsC - -phsC Start 1=Start
2.3.6.2 LD0.TRPPTRC1 Global conditioning (1)
Table 29: LD0.TRPPTRC1 Global conditioning (1)
IEC 61850 name
SA name Description Values
LD0.TRPPTRC1
.Op.general - Operate input signal 1=Operate
.Tr.general - Trip output signal 1=Trip
2.3.6.3 LD0.TRPPTRC2 Global conditioning (2)
Table 30: LD0.TRPPTRC2 Global conditioning (2)
IEC 61850 name
SA name Description Values
.Op.general - Operate input signal 1=Operate
.Tr.general - Trip output signal 1=Trip
Section 2 1MRS757660 A
DNP3 data mappings
30 RET620
Point List Manual