2.5.6 Protected related functions
2.5.6.1 DR.RDRE1 Disturbance recorder values
Table 173: DR.RDRE1 Disturbance recorder values
IEC 61850 name SA name Description Values S Arg 1,2,3,4
DR.RDRE1
.FltNum.stVal - Number of recordings 0…65535 R 0,65535,0,65535
.MemUsed.stVal - Rec. memory used 0…100 [%] R 0,100,0,100
2.5.6.2 LD0.SECRSYN1 Synchrocheck line and bus state
Table 174: LD0.SECRSYN1 Synchrocheck line and bus state
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.SECRSYN1
.EnSt.stVal - Energization state 0…4 R 0,4,0,4
2.5.7 Physical and raw I/O data
2.5.7.1 LD0.XRGGIO105 RTD inputs
Table 175: LD0.XRGGIO105 RTD inputs
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.XRGGIO105
.AnIn1.instMag AI_VAL1 RTD input 1
-10000…
10000 R -1E4,1E4,-1E4,1E4
.AnIn2.instMag AI_VAL2 RTD input 2
-10000…
10000 R -1E4,1E4,-1E4,1E4
.AnIn3.instMag AI_VAL3 RTD input 3
-10000…
10000 R -1E4,1E4,-1E4,1E4
.AnIn4.instMag AI_VAL4 RTD input 4
-10000…
10000 R -1E4,1E4,-1E4,1E4
.AnIn5.instMag AI_VAL5 RTD input 5
-10000…
10000 R -1E4,1E4,-1E4,1E4
.AnIn6.instMag AI_VAL6 RTD input 6
-10000…
10000 R -1E4,1E4,-1E4,1E4
.AnIn7.instMag AI_VAL7 RTD input 7
-10000…
10000 R -1E4,1E4,-1E4,1E4
.AnIn8.instMag AI_VAL8 RTD input 8
-10000…
10000 R -1E4,1E4,-1E4,1E4
1MRS757660 A Section 2
DNP3 data mappings
RET620 69
Point List Manual