2.5.3.3 LD0.TPOSSLTC1 Tap changer position value
Table 162: LD0.TPOSSLTC1 Tap changer position value
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.TPOSSLTC1
.TapPos.valWTr.posVal TAP_POS Tap changer position -64…63 R -64,63,-64,63
2.5.4 Metering and measurand functions
2.5.4.1 LD0.CMMXU1 Phase currents (1)
Table 163: LD0.CMMXU1 Phase currents (1)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.CMMXU1 Phase-to-ground current
.A.phsA.instCVal.mag I_INST_A -phsA magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.A.phsB.instCVal.mag I_INST_B -phsB magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.A.phsC.instCVal.mag I_INST_C -phsC magnitude 0.00..40.0 [xIn] R 0,40,0,4000
2.5.4.2 LD0.CMMXU2 Phase currents (2)
Table 164: LD0.CMMXU2 Phase currents (2)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.CMMXU2 Phase-to-ground current
.A.phsA.instCVal.mag I_INST_A -phsA magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.A.phsB.instCVal.mag I_INST_B -phsB magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.A.phsC.instCVal.mag I_INST_C -phsC magnitude 0.00..40.0 [xIn] R 0,40,0,4000
2.5.4.3 LD0.CSMSQI1 Sequence of currents
Table 165: LD0.CSMSQI1 Sequence of currents
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.CSMSQI1 Sequence of currents
.SeqA.c1.instCVal.mag I1_INST -Positive magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.SeqA.c2.instCVal.mag I2_INST -Negative magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.SeqA.c3.instCVal.mag I3_INST -Zero magnitude 0.00..40.0 [xIn] R 0,40,0,4000
Section 2 1MRS757660 A
DNP3 data mappings
66 RET620
Point List Manual