EasyManua.ls Logo

ABB ret650 - Transformer Winding, Earthed through Zig-Zag Earthing Transformer; Transformer Winding, Solidly Earthed

ABB ret650
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
magnetizing inrush currents
overexcitation magnetizing currents
load tap changer
external and internal phase faults which do not involve earth
symmetrical overload conditions
Due to its features, REFPDIF is often used as a main protection of the transformer
winding for all faults involving earth.
6.2.2.1 Transformer winding, solidly earthed
M13048-3 v10
The most common application is on a solidly earthed transformer winding. The
connection is shown in Figure
34.
IEC09000109-4-EN.vsd
REFPDIF
I3PW1CT1
I3P
IdN/I
Protected
winding
IEC09000109-4-EN V2 EN-US
Figure 34: Connection of the low impedance Restricted earth fault function
REFPDIF for a directly (solidly) earthed transformer winding
6.2.2.2 Transformer winding, earthed through zig-zag earthing transformer
M13048-8 v10
A common application is for low reactance earthed transformer where the earthing
is through separate zig-zag earthing transformers. The fault current is then limited
to typical 800 to 2000 A for each transformer. The connection for this application
is shown in figure 35.
Section 6 1MRK 504 169-UEN A
Differential protection
94 Transformer protection RET650 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB ret650

Related product manuals