EasyManua.ls Logo

ABB ret650 - Transformer Application Example

ABB ret650
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[ ] = + ×
-
>
æ ö
ç ÷
ç ÷
ç ÷
æ ö
ç ÷
ç ÷
è ø
è ø
p
A
t s B k
i
C
in
EQUATION1189 V1 EN-US (Equation 31)
Further description can be found in the technical reference manual.
tPRCrvx, tTRCrvx, tCRCrvx: Parameters for user programmable of inverse reset
time characteristic curve. Further description can be found in the technical
reference manual.
7.4.3.6 Transformer application example
SEMOD55591-4 v8
Two main cases are of interest when residual overcurrent protection is used for a
power transformer, namely if residual current can be fed from the protected
transformer winding or not.
The protected winding will feed earth-fault (residual) current to earth faults in the
connected power system. The residual current fed from the transformer at external
phase-to-earth faults is highly dependent on the total positive and zero-sequence
source impedances. It is also dependent on the residual current distribution between
the network zero-sequence impedance and the transformer zero-sequence
impedance. An example of this application is shown in Figure
54.
IN>
alt
Three phase CT
summated
Single CT
YN/D or YN/Y
transformer
en05000490.vsd
IEC05000490 V1 EN-US
Figure 54: Residual overcurrent protection application on a directly earthed
transformer winding
In this case the protection has two different tasks:
1MRK 504 169-UEN A Section 7
Current protection
Transformer protection RET650 2.2 IEC 129
Application manual

Table of Contents

Other manuals for ABB ret650

Related product manuals