11.1.3.4 Proxy for signals from switching device via GOOSE XLNPROXY
GUID-7C253FE7-6E02-4F94-96C7-81C9129D925D v1
The SwitchType setting controls the evaluation of the operating capability. If
SwitchType is set to Circuit Breaker, the input OPCAP is interpreted as a breaker
operating capability, otherwise it is interpreted as a switch operating capability.
Table 23: Operating capability values for breaker/switches
Value Breaker operating capability, CbOpCap Switch operating capability, SwOpCap
1 None None
2 Open Open
3 Close – Open Close
4 Open – Close – Open Close and Open
5 Close – Open – Close – Open Larger values handled as 4, both Close and
Open
6 Open – Close – Open – Close – Open
7 more
tStartMove is the supervision time for the apparatus to start moving after a
command execution is done from the SCSWI function. When the time has expired,
the command supervision is reset, and a cause-code is given.
During the tIntermediate time, the position indication is allowed to be in an
intermediate (00) state. When the time has expired, the command supervision is
reset, and a cause-code is given. The indication of the mid-position at SCSWI is
suppressed during this time period when the position changes from open to close or
vice-versa if the parameter SuppressMidPos is set to On in the SCSWI function.
In most cases, the same value can be used for both tStartMove and tIntermediate as
in the source function. However, tStartMove may need to be increased to
accommodate for the communication delays, mainly when representing a circuit
breaker.
11.2 Voltage control
SEMOD158732-1 v2
11.2.1 Identification
SEMOD173054-2 v5
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Automatic voltage control for tap
changer, single control
TR1ATCC
U
IEC10000165 V1 EN-US
90
Tap changer control and supervision, 6
binary inputs
TCMYLTC - 84
Section 11 1MRK 504 169-UEN A
Control
190 Transformer protection RET650 2.2 IEC
Application manual