OutType: Steady or Pulsed.
tPulse: In case of a pulsed output, it gives the length of the pulse (in seconds).
tDelay: The delay between the UP or DOWN activation signal positive front and
the output activation.
StopAtExtremes: Sets the behavior of the switch at the end positions – if set to
Disabled, when pressing UP while on first position, the switch will jump to the last
position; when pressing DOWN at the last position, the switch will jump to the first
position; when set to Enabled, no jump will be allowed.
11.4  Selector mini switch VSGAPC
SEMOD158754-1 v3
11.4.1  Identification
SEMOD167850-2 v4
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Selector mini switch VSGAPC - 43
11.4.2  Application
SEMOD158803-5 v8
Selector mini switch (VSGAPC) function is a multipurpose function used in the
configuration tool in PCM600 for a variety of applications, as a general purpose
switch. VSGAPC can be used for both acquiring an external switch position
(through the IPOS1 and the IPOS2 inputs) and represent it through the single line
diagram symbols (or use it in the configuration through the outputs POS1 and
POS2) as well as, a command function (controlled by the PSTO input), giving
switching commands through the CMDPOS12 and CMDPOS21 outputs.
The output POSITION is an integer output, showing the actual position as an
integer number 0 – 3, where 0 = MidPos, 1 = Open, 2 = Closed and 3 = Error.
An example where VSGAPC is configured to switch Autorecloser on–off from a
button symbol on the local HMI is shown in figure
86. The I and O buttons on the
local HMI are normally used for on–off operations of the circuit breaker.
Section 11 1MRK 504 169-UEN A
Control
236 Transformer protection RET650 2.2 IEC
Application manual