13.5.3  Setting guidelines
IP14841-1 v1
M12811-3 v3
The input parameters for the Event function (EVENT) can be set individually via
the local HMI (Main Menu/Settings / IED Settings / Monitoring / Event
Function) or via the Parameter Setting Tool (PST).
EventMask
 (Ch_1 - 16)
M12811-5 v3
The inputs can be set individually as:
• NoEvents
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, the EVENT function makes the reporting decision (reporting
criteria for integers have no semantic, prefer to be set by the user)
LONChannelMask
 or 
SPAChannelMask
M12811-15 v2
Definition of which part of the event function block that shall generate events:
• Off
• Channel 1-8
• Channel 9-16
• Channel 1-16
MinRepIntVal
 (1 - 16)
M12811-29 v3
A time interval between cyclic events can be set individually for each input
channel. This can be set between 0 s to 3600 s in steps of 1 s. It should normally be
set to 0, that is, no cyclic communication.
M12811-34 v1
It is important to set the time interval for cyclic events in an
optimized way to minimize the load on the station bus.
13.6  Disturbance report DRPRDRE
IP14584-1 v2
13.6.1  Identification
M16055-1 v8
Function description
IEC 61850 identification IEC 60617
identification
ANSI/IEEE C37.2
device number
Disturbance report DRPRDRE - -
Disturbance report A1RADR - A4RADR - -
Disturbance report B1RBDR - B22RBDR - -
1MRK 504 169-UEN A Section 13
Monitoring
Transformer protection RET650 2.2 IEC 285
Application manual