EasyManua.ls Logo

ABB ret650 - Logic Rotating Switch for Function Selection and LHMI Presentation SLGAPC; Identification; Application; Setting Guidelines

ABB ret650
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.3 Logic rotating switch for function selection and
LHMI presentation SLGAPC
SEMOD114936-1 v4
11.3.1 Identification
SEMOD167845-2 v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logic rotating switch for function
selection and LHMI presentation
SLGAPC - -
11.3.2 Application
SEMOD114927-4 v6
The logic rotating switch for function selection and LHMI presentation function
(SLGAPC) (or the selector switch function block, as it is also known) is used to get
a selector switch functionality similar with the one provided by a hardware multi-
position selector switch. Hardware selector switches are used extensively by
utilities, in order to have different functions operating on pre-set values. Hardware
switches are however sources for maintenance issues, lower system reliability and
extended purchase portfolio. The virtual selector switches eliminate all these
problems.
SLGAPC function block has two operating inputs (UP and DOWN), one blocking
input (BLOCK) and one operator position input (PSTO).
SLGAPC can be activated both from the local HMI and from external sources
(switches), via the IED binary inputs. It also allows the operation from remote (like
the station computer). SWPOSN is an integer value output, giving the actual output
number. Since the number of positions of the switch can be established by settings
(see below), one must be careful in coordinating the settings with the configuration
(if one sets the number of positions to x in settings – for example, there will be
only the first x outputs available from the block in the configuration). Also the
frequency of the (UP or DOWN) pulses should be lower than the setting tPulse.
From the local HMI, the selector switch can be operated from Single-line diagram
(SLD).
11.3.3 Setting guidelines
SEMOD115063-294 v6
The following settings are available for the Logic rotating switch for function
selection and LHMI presentation (SLGAPC) function:
Operation: Sets the operation of the function On or Off.
NrPos: Sets the number of positions in the switch (max. 32).
1MRK 504 169-UEN A Section 11
Control
Transformer protection RET650 2.2 IEC 235
Application manual

Table of Contents